Zimmer Dry-Electric Vaporizer
Dry-electric means no water and no glycol to maintain, giving more reliable operation and less maintenance than other vaporizer types. If the unit ever clogs it can be cleaned on site without removal.
Technical specification
| Vaporizer type | Indirect, dry-electric, feed out |
|---|---|
| Hazardous area | Class I, Division 1, Group D, T3; Ex db IIA T3 Gb (Zone 1) |
| Approvals | UL/ULc, CE (ATEX & IECEx), PED |
| Capacity | 25 / 40 / 50 / 100 / 150 kg/hr |
| Capacity (US Gal/hr) | 12.5 / 20 / 25 / 50 / 75 |
| Capacity (MMBTU/hr) | 1.1 / 1.8 / 2.2 / 4.5 / 6.8 |
| Liquid inlet | 1/2" FNPT (Z25–Z50), 3/4" FNPT (Z100–Z150) |
| Vapour outlet | 1/2" FNPT (Z25–Z50), 3/4" FNPT (Z100–Z150) |
| Design pressure (MAWP) | 250 psig / 17.2 barg |
| Relief valve set point | 250 psig / 17.2 barg |
| Hydrostatic test pressure | 375 psig / 25.9 barg |
| Shipping weight | 30–80 kg depending on model |
Key points
- Energy-efficient self-modulating heaters use only the required energy
- Easy access to all maintainable components
- Dry-electric design — no water, no glycol to maintain
- Multiple mounting options
- 25 to 150 kg/hr, easily added in parallel for greater capacity
- Start-up in less than 60 seconds
Specifications are taken from the manufacturer’s published data and may change without notice. Confirm dimensions, materials and approvals with our team before ordering.